Aperçu
Fonctionnalités
- Surveillance de l’etat des vannes ;
- Controle de la position des vannes (Pourcentage d’ouverture/fermeture) ;
- Installation sur l’equipement existant ;
Outdoor IP66+Ex ou IP65
Autonome jusqu'a 10 ans
Documentation
Manuel d'utilisation Ouvrir dans Wiki ↗
ROSSMA IIOT-AMS Dry contact VPM meter-switch is an autonomous device equipped with sensitive elements designed for monitoring the state and position of wedge and mechanical valves, with wireless data transmission.
Current data is transmitted wirelessly at a set interval (once per day by default), and also instantly when the input state changes. Read values are stored in the meter-switch memory and transmitted during scheduled communication sessions with the LoRaWAN network at the configured interval.
Capabilities
- Valve state monitoring
- Operation from built-in battery
- Wireless data transmission via LoRaWAN/NB-IoT
- Instant transmission on state change
- Built-in temperature sensor
- Autonomous operation up to 10 years
Technical Specifications
- Power type: 14 A/h; 126 A/h; 168 A/h; DC 3.3V
- Communication interval/14 A/h battery discharge time: 1 min./90 days, 2 min./180 days, 10 min./300 days, 1 hour/3 years 150 days
- Operating temperature range: -55…+85°C
- Built-in temperature sensor: yes (sent with every connection)
- Antenna type: internal
- Supply voltage: built-in 3.6 V battery, capacity 14 A/h, form factor: D
- Built-in battery charge measurement: yes (sent with every connection)
- Housing dimensions, mm: 80×75×55
- Mounting: cable ties and mounting ears
LED Indication
The meter-switch has indicators ACT (trigger), Lora (sending/receiving data via LoRaWAN network). The meter-switch has a RESET button – device reset, pressing which causes device reboot.
First Start
ATTENTION! Calibration is mandatory for proper device operation. Without calibration, VPM cannot correctly determine valve position.
Connecting the meter-switch to power must be done in the following order:
- Mount the meter-switch on the valve according to mounting type
- Unscrew screws (4 pcs) securing cover to housing base
- Remove cover
- Set valve to extreme position by turning wheel fully right or left until it stops
IMPORTANT! Before powering on, ensure the valve is in extreme position (fully open or fully closed).
- Turn on battery power
- Enable "Calibration" mode by installing jumper on contacts. When calibration mode is enabled, ACT indicator will light up
- Perform full open/close cycle of the valve, returning it to initial position (position before installing jumper)
- Disable "Calibration" mode by removing jumper from contacts
- Check indication:
- One long indication - calibration successful ✅
- Ten short indications + two long indications - number of valve open-close rotations does not match
- Ten short indications + three long indications - no rotation was performed
On calibration error: Repeat procedure from step 4. Ensure valve completes full open/close cycle.
- Close cover
TIP: Do not close cover until successful calibration! This allows quick procedure repetition if necessary.
Configuration and programming go to
Description :
Le dispositif de commutation ROSSMA IIOT-AMS Dry Contact VPM est un appareil autonome equipe d’elements sensibles, concu pour surveiller l’etat et la position des vannes a coin et mecaniques, avec transmission de donnees sans fil.
L’appareil peut etre utilise dans des installations industrielles, des infrastructures municipales et des endroits difficiles d’acces. L’appareil fonctionne dans des conditions climatiques et meteorologiques severes.
L’appareil est concu pour une utilisation en zones non dangereuses et dangereuses. Les appareils antideflagrants ont une protection de type « protection renforcee de type e ».
L’equipement est inscrit au registre du Ministere de l’Industrie et du Commerce de la Federation de Russie en tant qu’equipement fabrique en Federation de Russie (Certificat 48859/11 du 11.06.2021).
Logiciel
Application configurateur pour la configuration à distance des dispositifs de commutation ROSSMA® IIOT-AMS